Title: Effect of Fire Exposure to A Semi-Infinite Plate on Unexposed Surface Temperature
Authors: Suman, B M
Kumar, Sandeep
Keywords: 2011
Fire exposure
Surface temperature
Issue Date: 4-Jan-2012
Abstract: The success of fire design depends upon the accurate prediction of temperature level of fire. The temperature at unexposed surface depends upon the temperature of fire at exposed surface, Response factor, duration of time and thermo-physical properties of the plate. The Study has been carried out for transient heat flow in semi-infinite slab by assuming the fire at 800oC at exposed surface of 10 cm thick Autoclave aerated concrete and result of the study states that after thirty minutes of fire exposure, the temperature of unexposed surface rises from 20oC to 50oC.
Description: Proceedings of National Conference November 3-4, 2011. FIRE SCIENCE AND TECHNOLOGY - RESEARCH & ITS IMPLEMENTATIONS Published by : CSIR- Central Building Research Institute, Roorkee